Surge protector designed to protect a single LAN line from the effects of surges and lightning strikes. It is compatible with Ethernet networks of the 10Base-T and 100Base-T standards, used in connections with PCs, CCTV system cameras, industrial and building automation devices, as well as other consumer devices. It features direct grounding of large surge currents individually from each conductor, without the often-used intermediary elements that weaken surge resistance and have a significant impact on emitting or absorbing electromagnetic interference.

Three levels of protection in the data line using MOSFET technology effectively protect sensitive network interface circuits and introduce an additional separating buffer in case of large potential differences between the LAN switch and individual endpoints. Furthermore, MOSFET technology reduces the potential level that reaches the protected device (Voltage protection level UP) during a surge to a value that is only slightly higher than the rated operating voltage (Un).

Built-in PoE power protection circuits eliminate voltage spikes between transmission pairs 1,2 - 3,6 and pairs 4,5 - 7,8, which in 100Mbit networks are used solely for PoE power supply. They have been grouped to simplify the protection circuit, treating one pair as a single circuit line. The PoE protection circuits safeguard LAN endpoint devices from damage due to surges caused by lightning strikes or uncontrolled voltage increases, for example, due to a failure of the PoE power supply. The solutions used are completely neutral to any PoE standard and protect each of them, including Hi PoE.

PTF-51-EXT/PoE is intended for installation near LAN endpoint devices such as: PCs, PLC controllers, IPC cameras, radio transmitters, Internet of Things devices. Proper grounding using a PE line is necessary for correct operation, preferably with the shortest, dedicated grounding point. It is important to follow the directional operation of the protective function described in the user manual and not to reverse the connections of the device in the LAN installation, as this may cause improper operation or even damage.

PTF-51-EXT/PoE ensures continuity of the FTP cable shield between the input and output and additionally grounds the charge that appears between the shield and the ground. Since it is recommended to ground the FTP cable shield only on one side, the shield on the protector side is galvanically isolated at a level of 90VDC during normal operation.

Surge protector for HikVision cameras

To protect a single LAN line, two 1-channel protectors can be used, installed at both ends of the cable and properly grounded. In the case of needing to protect multiple LAN circuits, it is recommended to use a multi-channel limiter on the LAN switch side and single-channel ones on the endpoint devices side.

Surge protection for CCTV installations

If a protector from the EXT series is used on the side of external IP cameras, a multi-channel protector of at least the PRO series should be used on the LAN switch side; otherwise, the protection of the LAN switch will be insufficient.

If EXT series protections are connected to a LAN patch panel, it must be based on Keystone type connectors. Standard patch panels with LSA (Krone) sockets have too low impact resistance of the printed circuits and may be damaged.

Product tested according to categories D1, C2, C1, B2. It is intended for use at the boundaries of LPZ0/LPZ1 zones or higher.

 

Technical Specification

PARAMETER NAME
VALUE
Data line
Number of LAN channels
1
Supported Ethernet standards 10Base-T, 100Base-T
Used with cabling FTP, UTP of any category
Input connector (unprotected side) Shielded RJ-45 socket
Output connector (protected side) Shielded RJ-45 socket
Number of protection stages 3 (GDT, MOSFET, TVS)
Rated DC voltage (line-ground) UN 90V DC
Maximum continuous operating voltage (line-ground) UC 110V DC
C1: Protection level 1kV/μs (line-ground) UP 600V
C2: Discharge current (8/20µs, line-ground) lmax / conductor
2.5kA (max)
D1: Maximum lightning current (10/350µs, line-ground) Iimp 1kA
Rated DC voltage (line-line) UN 3.3V DC
Maximum continuous operating voltage (line-line) UC 3.5V DC
B2: Protection level 1kV/μs (line-line) UP
<8V
C1: Discharge current (8/20µs, line-line) Iimp 0.5kA
Decoupling element MOSFET fuse
Protected lines 1-2, 3-6
Capacitance (line-line) @1MHz 6-15pF
Capacitance (line-ground) @1MHz 1-2pF
Series resistance 6Ω / line
Rated current IN 300mA / line
PoE line
Rated DC voltage (line-line) UN 57V DC
Maximum continuous operating voltage (line-line) UC 64V DC
B2: Protection level 1kV/μs (line-line) UP 93V DC
C1: Discharge current (8/20µs, line-line) Iimp
0.5kA (option A), 250A (option B)
Rated DC voltage (line-ground) UN 90V DC
Maximum continuous operating voltage (line-ground) UC 110V DC
C1: Protection level 1kV/μs (line-ground) UP 600V
C2: Discharge current (8/20µs, line-ground) lmax / conductor
2.5kA (max)
Protected lines (pairs)
(1+2)-(3+6), (4+5)-(7+8)
PoE operating standard compliant with IEEE 802.3af/at/bt-type 3 (HiPoE, UPOE)
Power losses in PoE protection circuits

IEEE 802.3af, option A: 0.6W @48VDC
IEEE 802.3af, option B: 0.35W @48VDC

IEEE 802.3at, option A: 1.6W @54VDC
IEEE 802.3at option B: 0.6W @54VDC

IEEE 802.3bt, Type 3, option AB: 1.2W @54VDC

*) data for maximum expected load

Common features
Dimensions 65 x 30 x 40 (mm)
Application Protection of devices installed indoors / outdoors
Mounting method Free-standing / wall-mounted
Grounding method
Wire
IP rating IP40
Operating temperature -40ºC~60ºC

 

Product safety information Manufacturer information