Complete surge protection system for Gigabit network, 16-channel with RJ-45 sockets, 1GB Gigabit Ethernet LAN protector, designed for 6 categories, 1000Base-T and 1000Base-TX, PTF-616R-EXT/PoE
High quality 16-channel surge protector designed for Gigabit Ethernet networks based on 5, 5e and 6th cabling categories. It is built of four PTF-64-EXT modules mounted to the base PTU/PTF-6-RACK. It is usually mounted on the front of the 19" Rack cabinet, making it easier connect LAN ports by patchcords. In case of using IP-CCTV recorders it can be installed on the rear rail of the Rack cabinet, using LK-MOUNT angle brackets.
On the protected side (DEVICE) and unprotected side (LINE), RJ-45 sockets were used. This solution makes it easier to connect LAN cables to existing installations, and helps with maintenance process.
The PTF-64 series modules are very high-quality surge protection products with low signal losses. The use of multilayer PCBs and modern components in MOSFET technology resulted in compliance with the 6th category cabling standard and correct tests for 4x250MHz frequency.
Built-in 3-level surge protection using MOSFET technology, effectively eliminate overvoltages induced in cabling and introduce additional separation for ground loop potentials between LAN devices. MOSFET technology also reduces the level of overvoltages that reaches a protected device (UP voltage level) during overvoltage to a value that is a little higher than the rated operating voltage (Un). Obtaining such parameters is impossible in the case of the most commonly used conventional solutions.
Independent PoE protection circuits eliminate the overvoltages between 1.2 - 3.6 and 4.5 - 7.8 pairs in the LAN cable. This solution protects power supplies of LAN equipment against damage due to lightning surges or uncontrolled voltage increase, for example as a result of damage to the PoE power supply. The solutions used are compatible with each PoE standard, including Hi PoE.
Ensure proper grounding of the surge protector by connecting the supplied grounding cable to PE line. The optional PTU/PTF-COVER protects PCB from dust, it also provides an additional shield against interference.
The best level of surge protection is obtained by installing surge protectors on two sides of the LAN cable. Multi-channel surge protector at the LAN switch side and one-channel surge protector at the LAN device side - for example PTF-61-EXT/PoE.
Multi-channels surge protector for Giagabit Ethernet
Technical specification
PARAMETER NAME |
VALUE |
Data line | |
---|---|
Number of LAN channels | 16 |
Supported Ethernet standards |
10Base-T, 100Base-T, 1000Base-T, 1000Base-Tx |
Compatibility with cabling | Category 5, 5e i 6 (TIA) |
Input connector (unprotected side) | RJ-45 socket certified for 6 category |
Output connector (protected side) | RJ-45 socket certified for 6 category |
Rated Voltage DC (line-ground) UN | 90V DC |
Maximum Voltage (line-ground) UC | 110V DC |
Protection Level 1kV/μs (line-ground) UP | 600V |
Surge Current (8/20µS, line-ground ) Iimp | 2kA |
Rated Voltage DC (line-line) UN | 3.3V DC |
Maximum Voltage (line-line) UC | 3.5V DC |
Protection Level 1kV/μs (line-line) UP |
<8V |
Surge Current (8/20µS, line-line) Iimp | 75A (2kA after MOSFET reaction) |
Protected lines |
1-2, 3-6, 4-5, 7-8 |
Capacitnance (line-line) @1MHz | 5pF |
Capacitnance (line-ground) @1MHz | 2-3pF |
Decoupling | Super fast MOSFET fuse |
Serial resistance |
6Ω / line |
Rated Current IN | 300mA / line |
PoE Line | |
Rated Voltage DC (line-line) UN | 57V DC |
Maximum Voltage (line-line) UC | 64V DC |
Protection Level 1kV/μs (line-line) UP | 75V |
Surge Current (8/20µS, line-line) Iimp | 73A (2kA after MOSFET reaction) |
Rated Voltage DC (line-ground) UN | 90V DC |
Maximum Voltage (line-ground) UC | 110V DC |
Protection Level 1kV/μs (line-ground) UP | 600V |
Surge Current (8/20µS, line-ground ) Iimp | 2kA |
Protected pairs |
(1+2)-(3+6), (4+5)-(7+8) |
Supported PoE standards |
Compatible with all types including Hi PoE |
Common features | |
Dimensions | 480 x 41 x 130 (mm) |
Application | Indoors |
Mounting | 19" Rack cabinet |
Grounding method | Earthing conductor |
Operating temperature | -30ºC~60ºC |